Detailed Product Description
1. Summary
DSS/DTS51 Series Three Phase Static Energy Meter is designed with large-scale integrated circuit (LSI) and SMT technology. With advantages of high reliability and accuracy, it is widely used in measuring A.C. energy power.
DSS51/DTS51 Series Three Phase Static Energy Meter conforms to:
CEI IEC62052-11-2003 Electricity metering equipment (a.c.) General requirements, tests and test conditions Part 11: Metering equipment
CEI IEC62053-21-2003 Electricity metering equipment (a.c.) Particular requirements Part 21: Static meters for active energy (classes 1 and 2) equipment
CEI IEC62053-23-2003 Electricity metering equipment (a.c.) Particular requirements Part 23: Static meters for reactive energy (classes 2 and 3) equipment
DL/T6451997 Multi-function energy meter communication protocol
DSS51/DTS51 Series:
DSS51B,DTS51B Three Phase Active Energy Meter, register display
DXS51A,DXS52A Three Phase Reactive Energy Meter, register display
DSS(X)51B,DTS(X)51B, Three Phase Active&reactive Energy Meter, LCD display, RS485 port
DTS(X)51C Three Phase Active&reactive Energy Meter, LCD display,RS485 and Infrared port
2. Functions and Features
2.1 Energy measurement by phase; total energy is the summation of three phase energy pulses with less mutual interference
2.2 Reactive energy measurement via complementary passive phase circuit with high accuracy and reliability
2.3 New design adopted with less influence from frequency, voltage and harmonics on measurement accuracy; no calibration is needed during long working period
2.4 Three phase power supply with phase break indication. Measurement accuracy wont be affected if one or two phases are broken
2.5 Wide operating voltage range
2.6 Remote test impulse output
2.7 RS485 port: DSS(X)51B, DTS(X)51B
RS485 and infrared port: DTS(X)51C
3.Technical Specifications
Items | Technical Parameters |
Rated voltage | 220V, 100V |
Basic current | 1.5(6)A, 5(20)A, 10(40)A, 15(60)A, 20(80)A,30(100)A |
Start current | 0.4%Ib(CL1.0); 0.5%Ib(CL2.0) |
Frequency | 50Hz |
Accuracy | CL1.0 /2.0 |
Running with no load | Yes |
Power burden | ≤2W and 6VA |
Normal operating temp. | 20∼ +45 |
Limit operating temp. | 30∼ +55 |
RH | ≤85% |
Dimension | 288mm×170mm×73mm |