Welcome to ECBAY
Horizontal concealed fan coil unit
Horizontal concealed fan coil unit

1.Cooling&heating 2.Cooling capacity 7.2kw~15.3kw for option 3.2 or 4 pipes for different requriement

Product feature:

[High-efficiency]Heat exchanger uses the high quality thin-wall copper tube and high-efficiency fins, Cooperating with big air volume low noise fan to enhance the effect of  heat transfer.[Sturdy and durable]Use galvanized sheet shell, water-containing pipe use moulding process by one-step forming, Without welds and solder joints, Accord with waterproof standard heat preservation material overall adhesive in the defrosting pan, structure delicate and durable .[Quiet operation]Low noise motor is combined with galvanized multi-aerofoil centrifugal fan impeller by unique designed ,large air volume but low noise.[Flexible installation]The unit is designed to be light and handy, Lines are installed easily, Return air direction may change at any time, Can meet the needs of different space .[high-Efficient heating]Each model can be matched PTC auxiliary electrical heating with safe and reliable, To ensure that in the cold winter also can assure indoor warm as in spring.

Technical Specifications:

ModelFP-34WAFP-51WAFP-68WAFP-85WAFP-102WAFP-136WAFP-170WAFP-204WAFP-238WA
Powe supplyV/Ph/Hz220-240 /1 /50
Cooling capacityW18002700360045005400720090001086012600
Heating capacityW3300468054007120846011600139001650019200
Air flowing (m3/h)H34051068085010201360170020402380
M2603805206507701050135016201890
L17526037047556074092011301330
Power inputW3441627391118146182216
Water flowL/h3605206807809201280158018602160
Water resistancekPa71518232830223036
Fan& MotorTypeCentrifugal
Fan122223444
Motor111112222
NoisedB(A)353638404344454649
Coil pipeTypeCopper pipe Ø9.52
Pressure  Working pressure 1.6MPa
Inlet/Outlet pipeinchRC3/4"(DN20)
Drain pipeinchRC3/4"(DN20)
Dimensions(mm)L8409401040114012401440164017901940
W450
H246
Net weightkg151719273032384550
1. Cooling: Indoor DB=27°C, WB=19°C, water supply temp 7°C.2. Heating: Indoor DB=21°C, water supply temp 60°C.3. The air flow,cooling capacity and heating capacity are tested under ESP 12Pa and without filter.