it can be measured the flow rate of steam and air,coal gas, oxygen,compressed air... Diameter from 15~1200mm.
Nominal Diameter | Liquid | Gas | |||
(mm) | (in.) | Flow (m3/h) | Frequency(Hz) | Flow (m3/h) | Frequency(Hz) |
15 | 0.5 | 0.5 to 5 | 46 to 464 | 3.5 to 25 | 325 to 2320 |
20 | 0.75 | 1 to 10 | 40 to 396 | 5.5 to 50 | 218 to 1982 |
25 | 1 | 1.6 to 16 | 32 to 325 | 8.5 to 70 | 172 to 1420 |
40 | 1.5 | 2.5 to 25 | 13 to 130 | 22 to 220 | 115 to 1147 |
50 | 2 | 3.5 to 35 | 13 to 130 | 22 to 220 | 115 to 1147 |
65 | 2.5 | 6.5 to 68 | 9 to 93 | 36 to 320 | 96 to 854 |
80 | 3 | 10 to 100 | 8 to 82 | 50 to 480 | 61 to 583 |
100 | 4 | 15 to 150 | 6 to 65 | 70 to 640 | 45 to 417 |
125 | 5 | 27 to 275 | 5 to 47 | 200 to 1700 | 33 to 290 |
150 | 6 | 40 to 400 | 4 to 40 | 280 to 2240 | 27 to 221 |
200 | 8 | 80 to 800 | 3 to 33 | 580 to 4960 | 24 to 207 |
250 | 10 | 120 to 1200 | 3 to 26 | 970 to 8000 | 20 to 171 |
300 | 12 | 180 to 1800 | 2 to 22 | 1380 to 11000 | 17 to 136 |
Accuracy:
Liquid: ±1.0% of reading
Gas: ±1.0% of reading
Vapor Stream: ±1.5% of reading
Materials:
Housing: Standard - 304 Stainless Steel
Shedder Bar: 1Cr18Ni9Ti
Converter housing and case cover: Aluminum Alloy
Output Signal: (Where applicable)
Sensor: Pulse signal (Low Level: ≤1V; High Level: ≥6V)
Transmitter: 4 to 20 mA DC current signal
Signal Transmission Distance:≤500 m
Electrical Connections: ISO M20×1.5 Female
Explosion Proof Level:
Standard: ExdIIBT6
Protection Level: IP65
Vibration: ≤1.0 g
Ambient:
Temperature: -10°C to +55°C
Pressure: 86 to 106 KPa
Relative Humidity: 5% to 90%
Power Supply:
Sensor: +12V DC (Optional: +24V DC)
Transmitter: +24V DC
Field Display Type: Integral 3.2V Lithium Battery or +24V DC
Fluid Temperature and Pressure:
Temperature: Standard: -20°C to +70°C
Optional: -20°C to +250°C; -20°C to +350°C
Pressure: Fluid pressure should be limited according to flange rating.
LUCB-Coal gas flow meter