phase circuit using a static induction voltage clip. The static induction voltage clips are used to be able to clip on a clad
Product Features:
ISO, Patent & CE certificate OEM services available Function: phase detection (positive/negative) Display: LED Dimension (mm): 70*75*30 Weight(g): 270 Continuously using 200 hours Meets IEC-10101 (EN61010) ,CAT III (600V) safety requirement Electricity range: AC60~600V,40 Hz~70Hz( continuous sine wave input ) The highest detected voltage: AC600V Insulating Strength: 5.4kVrms Safety suitable for: 100MvaIntroduction
This is a phase detector, designed to perform phase sequence checks and live line checks of a 3-phase circuit using a static induction voltage clip.
The static induction voltage clips are used to be able to clip on a cladded wire.
It is small with a CAT 600V safety rating.
Red LED lamps are used to make the indication visible in dimly lit areas.
The direction of phase sequence can be checked easily using the LED lamps, which blink in order
Specifications
1). Basic Specifications
Function | Phase detection (positive/negative) |
Voltage detection method | Static induction |
Object to be connected | Insulated wire (nominal sectional area of the conductor: 2 to 120mm2, finished outer diameter: up to 17mm) |
Performance-guarantee voltage range | 3-phase, 70V to 600 VAC (sine wave,continuous) |
Operating frequency range | 45Hz to 66Hz |
2). Display
Phase-detection indication | Positive phase sequence: The four phase-sequence lamps blink order (clockwise) and the buzzer sounds intermittently. Negative phase sequence: The four phase-sequence lamps blink in order (counterclockwise) and the buzzer sounds continuously. |
Line-voltage indication | R-S lamp, S-T lamp |
Power indication | Power ON lamp: lights up (Power ON) blinks (Battery Low) |
3). General Specifications
Operating temperature and humidity | -10 to 40(32 to 104), 80%RH or less ( with no condensation) |
Storage temperature and humidity | -20 to 60 (-4 to 140), 80%RH or less (with no condensation) |
Location for use | Altitude up to 2000m(6562 feet), indoors |
Maximum rated voltage to earth | 600V |
Dielectric strength | 5.4kVrms |
Power supply | Rated supply voltage 1.5VDC×2 Two AA size batteries |
Maximum rated power | 300mVA |
Continuous operating time* | Approx.70 hours(Power ON, Standby state, using R6P manganese battery) *Battery life |
Auto Power Off (This function can not Be canceled.) | The power will be turned off automatically if the Instrument remains idle for 15 minutes after the power is turned on. To reset, turn the power on again using the Power ON switch. |
Options | Carrying case, Strap*, Spiral tube*, Instruction manual, Two R6P manganese batteries. *Attaching as the occasion demands. |
Cable length | Approx. 0.7m |
Dimensions and mass | Approx. 70W×75H×30Dmm(2.76W×2.95H×1.18D) (excluding projections), Approx. 200g(7.1oz) |
Applicable standards | Safety EN61010-1:2001,EN61010-031:2002 Pollution degree2, Measurement category CAT III(600V)(anticipated transient overvoltage 6000V) EMC EN61326:1997+A1:1998+A2:2001 |
Packing | Phase Detector: 1 piece; strap: 1 piece; Carrying Case: 1 piece |
ETCR1000A Non Contact 3 Phase Rotation Tester Indicator #2