GZS1 indoor metal-clad withdrawable switchgear is a complete power distribution device for 3.6~24 Specifications
High voltage Switchgear GZS1 type similar as ABB ZS series
GeneralGZS1 indoor metal-clad withdrawable switchgear(hereinafter short as switchgear)is a complete power distribution device for 3.6~24kV,3-phase AC 50Hz,single-bus and single-bus sectionalized system. It is mainly used for power transmission of middle/small generators in power plants; power receiving, transmission for substations in power distribution and power system of factories, mines and enterprises, and starting of large high-voltage motor, etc.,so as to control, protect and monitor the system. The switchgear meets IEC298,GB3906-91.In addition to be used with domestic VS1 vacuum circuit breaker, it can also be used with VD4 from ABB,3AH5 from Siemens domestic ZN65A,and VB2 from GE, etc.,it is truly a power distribution device with good performance.
In order to meet the requirement for wall mounting and front-end maintenance, the switchgear is equipped with a special current transformer, so that the operator can maintain and inspect it in front of the cubicle.
Service environmenta) Air temperature: Maximum temperature: +40°C; Minimum temperature:-15°C
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude: 1000M.
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake Main technical specifications
No | Item | Unit | Parameter | ||
1 | Rated voltage | kV | 7.2kV, 12 kV,17.5kV,24kV | ||
2 | Rated frequency | Hz | 50/60 | ||
3 | Rated current | A | 630,1250,1600,2000,2500,3150,4000 | ||
4 | Branch busbar Rated current | A | 630,1250,1600,2000,2500,3150,4000 | ||
5 | Main busbar Rated current | A | 630,1250,1600,2000,2500,3150,4000 | ||
6 | 1min Power frequency withstand voltage | wet | kV | 38 | 50/60 |
dry | kV | 48 | 60/65 | ||
7 | Lightning impulse withstand voltage | kV | 75 | 95/125 | |
8 | Rated short circuit breaking current (peak) | kA | 40/50/63/80/100 | ||
9 | Short time withstand current(4s) | kA | 20/25/31.5/40 | ||
10 | Protection type | IP4X for housing |
high voltage switchgear