Welcome to ECBAY
DR series 75w guide rail switching power supply
DR series 75w guide rail switching power supply

can be installed on DIN rail: TS-35/7.5or TS-35/15

Guide rail type switching power supply 75W

Features:                                                                                                                                                                                                               

·Universal AC input ·Small volume,low weight, high efficiency·Protections: short circuit/over load/over voltage·Cooling by free air convection·Can be installed on DIN rail: TS-35/7.5or TS-35/15·LED indicator for power on·100% full load burn-in test·2 Year warranty 

DR-75W
ModelDR-75-12DR-75-24DR-75-48
Output DC voltage12V24V48V
 Voltage tolerance±2%±1%±1%
 Rated current6.3A3.2A1.6A
 Current range0~6.3A0~3.2A0~1.6A
 Rated power76W76.8W76.8W
 Ripple&noise100mvp-p150mvp-p200mvp-p
 DCvoltage ADJ.range-9%~+10%±10%±10%
Input Voltage range90~264VAC, 127~373VDC
 Frequency47~63Hz
 AC current1.6A/110VAC, 0.96A/220VAC
 Efficiency79%81%84%
 Inrush currentCold start current  20A/115VAC,40A/230VAC
 Leakage current< 1mA/240VAC
Protection Over loadabove 110%~150% rated power
protection type: rated current limit, auto-recovery after fault condition is removed
 Over voltage15.6~17.8V30.6~33.2V54.8~56.6V
protection type: cutoff output, recovery after restart power
Environment Working temp,humidity-20°C~+60°C, 20%~90%RH
 Storagetemp,humidity

-40°C~+85°C, 10%~95%RH non-condensing

 Withstand vibration10~500Hz, 2G 10min/1cycle, period for 60 minutes, each axes
Safety Withstand voltageI/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
 Isolated resistanceI/P-O/P,I/P-FG,O/P-FG: 100M ohms/500VDC
Fitstandard Safety standardFit UL1012
 EMC standardmeet EN55022, CLASS A
Others Dimension55.5*125.2*100mm (L*W*H)
 Weight/packing0.6kg/20pcs/13kg/0.046m³/1.64CUFT
Note 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
 3. Tolerance : includes set up tolerance, line regulation and load regulation.

DR series 75w guide rail switching power supply

Ads by Google


About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.