Chapter 1. General introduction
SCD508 series intelligent temperature controller can be applied in the control and
alarm in range of -200~1750°C. It can used in the controller and alarm of pressure,
discharge, liquid level and humidity etc, parameters when fitted with corresponding
transmitter.
The key features include:
1. Manifold signals including signals of thermocouple, resistance thermometer detector
(RTD), direct voltage, direct current, resistance can be input freely.
2. The input uses digital correction system; there is non-linear correction form of
communal used thermocouple and resistance thermometer detector.
3. Freely changeable with on-off control or PID control with configurable direct reverse
action modes. It has the self-tuning function of PID parameter.
4.Control output supports relay contact switch, solid-state relay (SSR) driving voltage, and
single-phase thyristor zero-crossing trigger signal etc.
5. One way of programmable alarm outputs is provided with a number of alarm modes
including higher -limit, lower limit. In addition, the alarm feature can also be
temporarily disabled when applying the power.
6. Comprehensive self-detection and protection-- In case of error, it provides automatic
Chapter 2. Type and designation
Chapter 3. Technical Parameters(freely changeable with keypad)
Input type | Code | Measuring range | Input type | Code | Measuring range |
Thermocouple (TC) | K | -50°C~+1350°C | DC voltage (U) | 0-5V | Customized range within -1999~+999 |
S | -50°C~+1750°C | 1-5V | |||
E | -50°C~+800°C | ||||
J | -50°C~+1000°C | ||||
resistance thermometer detector (RTD) | Cu50 | -50°C~+150°C | DC current(I) | 0-20mA | |
Pt100 | -200°C~+850°C | 4-20mA |
Chapter 4. Shape and Hole cutout dimension
Panel dimension code | Panel dimension | Case dimension |
| ||||
W | H | W | H | D | W | H | |
A | 96 | 96 | 91 | 91 | 100 | 92 | 92 |
D | 72 | 72 | 67 | 67 | 100 | 68 | 68 |
E | 48 | 96 | 44 | 90 | 100 | 45 | 92 |
F | 96 | 48 | 90 | 44 | 100 | 92 | 45 |
G | 48 | 48 | 44 | 44 | 100 | 45 | 45 |
H | 160 | 80 | 150 | 75 | 100 | 152 | 76 |
S | 80 | 160 | 75 | 150 | 100 | 76 | 152 |
Chapter 5. Instrument wiring
Wiring Diagram, SCD508-A.E.F.H.S series
Chapter 6. Ordering instructionsPlease take care to indicate the model, name, input specifications and orderingquantity in a clear and complete manner upon ordering.For example SCD508-A110-0~1200°Cshows that it is a digital indicating controller with panel dimension of 96×96mm,PID control relay contact switch output, one absolute value higher limitalarm relay output channel, input signal of K-division TC and measuringrange of 0~1200°C.