110kV Oil-immersed Power Transformer
110kV Oil-immersed Power Transformer

Economic or deluxe solution optional Better cost performance IEC Standards Criteria New factory for better price NVTC/ OLTC

REFERENCES

ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles – Specifications and test methods.

IEC 60076: Power transformers.

IEC 60044: Instrument transformers.

IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear.

IEC 60354: Loading guide for oil – immersed power transformers.

IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide.

IEC 60512: Connectors for electronic equipment.

Performance

110kV Two-Winding Power Transformer With NVTC/OLTC

Rated

Capacity

 (kVA)

Rated Voltage (kV)

Vector

 Group

Losses (W)

Impedance

 Voltage

 (%)

HV

Tapping

 Range

LVNo loadOn load
6300110 121±2×2.5%6.3 6.6 10.5 11YNd1180003690010.5
8000960045000
100001120053100
125001320063000
160001600077400
200001900093600
2500022400110700
3150026700133200
4000031800156600
5000037600194400
6300044600234000
110kV Three-Winding Power Transformer With   NVTC/OLTC

Rated

Capacity

 (kVA)

Rated Voltage (kV)

Vector

 Group

Losses (W)Impedance Voltage (%)
HV

Tapping

 Range

LVNo loadOn loadStep UpStep Down
6300

110 ±2×2.5%  

121 ±2×2.5%

35 38.5 ±2×2.5%6.3 6.6 10.5 11YNyn0d11960047700

HV-MV 17-18

HV-LV 10.5

MV-LV 6.5

HV-MV 10.5

HV-LV 17-18 MV-LV 6.5

80001150056700
100001360066600
125001600078300
160001930095400
2000022800112500
2500027000133200
3150032000157500
4000038200189000
5000045200225000
6300053600270000

INSULATION LEVELS

Nominal system voltage

(kV,   rms)

Highest system voltage

(kV,   rms)

Lightning Impulse withstand voltage, dry

(kV,   peak)

Power frequency withstand voltage, wet

(kV,   rms)

33

36

200

95

132

145

650/750 (internal/external)

275/325 (internal/external)

AUXILIARY SUPPLIES

Equipment generally rated for the following auxiliary power supplies:

(a)          Cooler control circuits:          220V, 240 V, single phase, 50Hz

(b)         Tap changer control:              220V, 240 V, single phase, 50Hz

(c)          Cooling fan motors:               380V, 415 V, three phase, 50Hz

(d)         Tap changer motor:               380V, 415 V, three phase, 50Hz

 

 ROUTINE TEST to IEC 60076 (to be done during acceptance testing at factory)

 

 

• Measurement of winding resistance

• Ratio test

• Vector group

• Separate source voltage withstand test

• Induced over-voltage

• Insulation resistance

• Oil leakage test on fully assembled transformer for 12 hours

• Measurement of impedance voltage

• Magnetic balance

• Measurement of no-load loss and current

• Measurement of load loss (at normal & extreme taps)

• Tests on on-load tap-changer

• Tests on on-load tap-changer remote control panel

• Efficiency at 50%, 75%, 100% loading at unity p.f and rated terminal voltage (Corrected to 75C)

• Lightning impulse withstand test

Type Tests to IEC 60076 (to be done during acceptance testing at factory)

• Temperature rise test – To be performed on one unit during acceptance testing.

Lightning Impulse Withstand Test is already listed under Routine Tests as per IEC 60076.